CMP vs CMR Cable: Key Differences Explained
CMP (plenum) and CMR (riser) are both fire-rated communications cable ratings under NEC Article 800, but they pass different fire tests. CMP must pass the stricter UL 910 test, which limits both flame spread and smoke. CMR must pass UL 1666, which tests flame climbing in a vertical shaft and does not measure smoke density. CMP can replace CMR anywhere, but CMR can never replace CMP.
This guide covers the technical differences contractors and IT managers need before ordering bulk cable: test standards, jacket and insulation materials, NEC sections, and real installation scenarios.
Quick answer: Choose CMP for any space used for environmental air, such as an open return-air ceiling. Choose CMR (or CMP) for vertical runs between floors. If a route crosses both, use CMP. Always buy cable that is third-party listed, and confirm requirements with your local inspector.
CMP vs CMR at a Glance
| CMP (plenum) | CMR (riser) | |
|---|---|---|
| Fire test | UL 910 / NFPA 262 (Steiner tunnel) | UL 1666 (vertical shaft) |
| What the test measures | Flame spread and smoke density | Flame propagation and temperature in a vertical run |
| Smoke requirement | Yes, strict limits | No smoke density limit |
| Typical jacket | Low-smoke flame-retardant PVC or fluoropolymer | Flame-retardant PVC |
| Typical insulation | Fluoropolymer (FEP) | Polyolefin or PVC; some use FEP |
| Allowed in plenums | Yes | No |
| Allowed in vertical risers | Yes | Yes |
| Substitution | Can replace CMR, CMG, CM, CMX | Can replace CMG, CM, CMX |
| Cost | Higher | Lower |
The Fire Tests: UL 910 vs UL 1666
UL 910 (CMP)
UL 910, also referenced as NFPA 262, is the Steiner tunnel test. Cable is laid in a roughly 25 ft horizontal tunnel with airflow while a burner runs for about 20 minutes. To pass, cable must meet limits on three results:
- Flame spread: no more than about 5 ft beyond the burner flame.
- Peak optical density (smoke): 0.5 or less.
- Average optical density (smoke): 0.15 or less.
The smoke limits are the key difference. Plenum spaces move air through a building, so smoke from burning cable can spread to occupied areas. CMP is designed so that very little smoke is produced.
UL 1666 (CMR)
UL 1666 simulates a fire in a vertical shaft that passes through floors. Cable is run up a shaft while a burner is applied at the base. To pass, flame must not travel past a set height (about 12 ft above the burner) and the temperature at that height must stay under a limit (about 850°F).
The purpose is to stop fire climbing from floor to floor. The test does not set a smoke density limit, which is why CMR is not allowed in plenums.
Test parameters above are summarized for guidance. Confirm exact values in the current standards.
Jacket and Insulation Materials
The fire rating is achieved through materials, and this is also what drives cost.
CMP construction
- Jacket: low-smoke, flame-retardant PVC or a fluoropolymer compound.
- Insulation: most CMP uses fluorinated ethylene propylene (FEP) on the conductors. FEP resists burning, produces little smoke, and has good electrical properties.
- Handling: fluoropolymer compounds are stiffer, especially in cold weather, and cost more.
CMR construction
- Jacket: flame-retardant PVC.
- Insulation: often polyolefin or PVC, which is cheaper than FEP.
- Variation: constructions differ by maker. Some CMR cable uses FEP insulation with a riser-rated jacket, so read the spec sheet instead of assuming from the rating alone.
A note on “LSZH”
LSZH (low smoke zero halogen) describes the chemistry of a jacket, not an NEC rating. An LSZH cable is only acceptable in a plenum if it is also marked and listed CMP. Look for the NEC marking on the jacket, not the marketing name.
NEC Code Sections That Apply
NEC Article 800 covers communications circuits. These are the sections people most often need:
| Topic | NEC reference |
|---|---|
| Cable in ducts, plenums, and other air-handling spaces | 300.22 |
| Spread of fire or products of combustion (penetrations, fire-stopping) | 300.21 |
| Installation of communications wires and cables | Article 800 (800.113 in many editions) |
| Cable applications and substitutions | Article 800 (800.154) |
| Listing and marking requirements | Article 800 (800.179 in the 2023 edition) |
Important: section numbers changed between NEC editions, and listing requirements were moved into Article 800 in the 2023 edition. Always check the edition your jurisdiction has adopted. Local amendments can add requirements, and the inspector (AHJ) has the final say.
The substitution hierarchy
CMP → CMR → CMG/CM → CMX. A higher-rated cable can replace a lower-rated one, never the reverse.
LP-rated cable for PoE
Newer NEC editions add limited-power (LP) markings, such as CMP-LP and CMR-LP. These relate to how much current a cable can carry in bundles for PoE applications. If you plan high-wattage PoE, check whether your project specification calls for LP-marked cable.
Real Installation Scenarios
| Scenario | Required rating | Reasoning |
|---|---|---|
| Open return-air ceiling in an office | CMP | Environmental air space (300.22) |
| Cable in a vertical shaft between three floors | CMR (or CMP) | Runs through more than one floor |
| Horizontal run in a closed wall on one floor | CM/CMG (or higher) | Not plenum, single floor |
| Route starts in a riser, then crosses a plenum ceiling | CMP for the plenum part | Highest-risk space governs |
| Ceiling with ducted return air (not open plenum) | Usually CMR/CM, but confirm | Ceiling space may not count as plenum |
| Mixed building where plans are unclear | CMP | Works in every space listed above |
Why many contractors default to CMP
Using CMP on every route removes the risk of a rating mistake, and it lets you stock one cable type. The extra cost is small compared with the cost of a failed inspection.
Cost Comparison: CMP vs CMR
Example 2026 bulk listing prices at 52Networks:
| 1000ft box | CMR (riser) | CMP (plenum) | Difference |
|---|---|---|---|
| Cat6 bare copper | ~$169–$175 | ~$199 | ~15–18% |
| Cat6A bare copper | ~$245 | ~$290–$319 | ~16–30% |
On a 20-box job, using CMP everywhere adds roughly $500 to $1,500 in cable. If an inspector rejects CMR in a plenum space, the cost is pulling out and replacing the cable and paying for re-inspection. In our 100-drop planning model, that was about $15,000 in labor alone. The labor number is an assumption, so use local quotes.
Verify Compliance: Buy ETL-Listed Cable
A “CMP” or “CMR” label on a listing page is not the same as third-party listing. Listing means an independent lab tested the cable and audits the factory. For commercial work, ask for listed cable and keep the paperwork for the inspector.
Where to find it: 52Networks carries bulk CMP and CMR cable, and many of its listings state ETL Listed, 100% solid bare copper, and a published spec sheet.
- CMP: Cat6 plenum · Cat6A plenum
- CMR: Cat6 riser · Cat6A riser
Pre-order checklist
- The jacket marking shows the rating (CMP or CMR), category, and listing mark.
- The spec sheet states conductor type. Look for bare copper, not copper-clad aluminum.
- You have the ETL listing documentation for your project file.
- The rating matches the most demanding space on the route.
- The inspector has confirmed the plenum and riser areas.
Frequently Asked Questions
What does CMP stand for?
CMP is the NEC marking for communications plenum cable, rated for air-handling spaces.
What does CMR stand for?
CMR is the NEC marking for communications riser cable, rated for vertical runs between floors.
Can CMP replace CMR?
Yes. CMP has the higher rating and is allowed wherever CMR is permitted.
Can CMR be used in a plenum?
No. CMR does not meet the smoke and flame limits for plenum spaces.
What is the difference between UL 910 and UL 1666?
UL 910 is a horizontal tunnel test that limits flame spread and smoke, used for CMP. UL 1666 is a vertical shaft test that limits flame climbing, used for CMR, and it has no smoke density limit.
Is LSZH cable the same as CMP?
No. LSZH describes the jacket chemistry. Only cable marked and listed CMP can be used in plenum spaces.
Does CMP perform better than CMR for data?
No. The rating affects fire and smoke behavior, not data speed or bandwidth.
Is ETL listing as good as UL listing?
Both come from nationally recognized testing labs, and ETL listing is commonly accepted as equivalent by inspectors. Confirm with your local authority.
Final Word
CMP and CMR differ in the test they pass and the smoke they are allowed to produce, not in data performance. Match the rating to the most demanding space on the cable’s route, buy listed cable with documentation, and use CMP when there is any doubt.
Prices were collected from public listings in November 2026 and may have changed. Fire code rules vary by NEC edition and local jurisdiction. Confirm requirements with your local authority before you order or install.
Related Projects
Read More
UncategorizedOctober 29, 2026
How to Build a Reliable Network Infrastructure for a Small Business
How to Build a Reliable Network Infrastructure for a Small Business
A reliable network infrastructure is essential for keeping a small business connected, productive, and secure. From computers and printers to cloud applications, security cameras, and wireless access points, every connected device depends on a network that performs consistently.Building a dependable...
UncategorizedNovember 18, 2026
Cat6A Plenum 1000ft Cost: What to Expect in 2026
Cat6A Plenum 1000ft Cost: What to Expect in 2026
If you’re ready to order, here is the short answer: a 1000ft box of unshielded, bare copper, listed Cat6A plenum cable costs roughly $290 to $550 in 2026. Shielded versions run about $500 to $780. Anything far below that range...
UncategorizedNovember 19, 2026